First name, Middle name, Last name, Scientific degree, Scientific rank, Current position. Full and brief name of the organization, The organization address.Broyda V.A. – candidate of technical sciences, associate professor E-mail: This e-mail address is being protected from spambots. You need JavaScript enabled to view it Babich E.K. – student E-mail: This e-mail address is being protected from spambots. You need JavaScript enabled to view it Kazan State University of Architecture and Engineering The organization address: 420043, Russia, Kazan, Zelenaya st., 1
Title of the articleDependencies for calculating the air-jet screen over an industrial bath
Abstract.Problem statement. The purpose of the study is to identify and present, in an accessible form for practical applications, the basic dependencies for the calculation of air screens over industrial baths obtained by the CFD method. The parameters of the interaction of a flat jet flow and a localizing slot outlet in air screens depend mainly on the geometric conditions: the distance between the supply and discharge device l, the distance from the axis of the air screen to the liquid mirror h, width of the slot outlet B. Results. The main results of the research consist in the dependences presented in the dimensionless form, which are required for the calculation of air screens over industrial baths. Such dependencies are given in the form of analytical formulas and in the form of graphs. Because of the complexity of the calculated flows, the analytical description is rather cumbersome and more suitable for a computer calculation program. Graphic materials are available for manual calculations. Conclusions. The significance of the results obtained for the ventilation of industrial buildings is to more fully and correctly take into account the geometric factors in the calculation of air screens over industrial baths. The examples illustrate how to apply the obtained dependencies.
Keywords.air-jet screen, flat jet flow, outlet, air flow, calculation.
For citations:Broyda V.A., Babich E.K. Dependencies for calculating the air-jet screen over an industrial bath // Izvestiya KGASU. 2017. №2(40) P.160-167.


New issues

 
Russian (CIS)English (United Kingdom)

Search

Vinaora Visitors Counter

mod_vvisit_countermod_vvisit_countermod_vvisit_countermod_vvisit_countermod_vvisit_countermod_vvisit_counter
mod_vvisit_counterToday34
mod_vvisit_counterYesterday99
mod_vvisit_counterThis week34
mod_vvisit_counterLast week638
mod_vvisit_counterThis month2239
mod_vvisit_counterLast month2890
mod_vvisit_counterAll days792091

Online (12 hours ago): 2
Your IP: 192.168.1.44
MOZILLA 5.0,
Today: Ноя 24, 2024